energies Article Propagation of Overvoltages in the Form of Impulse, Chopped and Oscillating Waveforms in Transformer Windings—Time and Frequency Domain Approach Marek Florkowski , Jakub FurgaΕ and Maciej Kuniewski * Department of Electrical and Power Engineering, AGH University of Science and Technology, al. Mickiewicza 30, 30-059 Kraków, Poland; [email protected] (M.F.); [email protected] (J.F.) * Correspondence: [email protected] Received: 26 November 2019; Accepted: 5 January 2020; Published: 8 January 2020 Abstract: This paper describes a comparison of overvoltage propagation in transformer windings. Expanding and evolving electrical networks comprise various classes of transient waveforms, related to network reconfigurations, failure stages and switching phenomena, including new sources based on power electronics devices. In particular, the integration of renewable energy sources—mainly solar and wind—as well as expanding charging and energy storage infrastructure for electric cars in smart cities results in network flexibility manifested by switching phenomena and transients propagation, both impulse and oscillating. Those external transients, having a magnitude below the applied protection level may have still a considerable effect on winding electrical insulation in transformers, mainly due to internal resonance phenomena, which have been the root cause of many transformer failures. Such cases might occur if the frequency content of the incoming waveform matches the resonance zones of the winding frequency characteristic. Due to this coincidence, the measurements were performed both in time and frequency domain, applying various classes of transients, representing impulse, chopped (time to chopping from 1 µs to 50 µs) and oscillating overvoltages. An additional novelty was a superposition of a full lighting impulse with an oscillating component in the form of a modulated wavelet. The comparison of propagation of those waveforms along the winding length as well as a transfer case between high and low voltage windings were analyzed. The presented mapping of overvoltage prone zones along the winding length can contribute to transformer design optimization, development of novel diagnostic methodology, improved protection concepts and the proper design of modern networks. Keywords: transformer windings; lightning; chopped; oscillating impulse; overvoltages; modulated wavelet; non-standard voltage waveforms 1. Introduction Reliability of electric power systems, on both transmission and distribution levels, is an actual research topic [1–12]. Transformers play a crucial role in electrical networks and belong to the class of equipment which is not quickly replaceable. The subject of the presented research is the propagation of overvoltages in the form of impulse, chopped and oscillating waveforms in transformer windings, considered both in the time and frequency domain. The experiments were performed on a distribution transformer exposed during normal operational conditions to several surge stresses in the form of full and chopped lightning as well as switching phenomena. On the other hand, the integration of renewable energy sources, such as solar and wind, and expanding charging and energy storage infrastructure for electric cars results in network reconfiguration and the immanently related propagation of transients, both impulse and oscillating, originating in power electronics devices. Energies 2020, 13, 304; doi:10.3390/en13020304 www.mdpi.com/journal/energies Energies 2020, 13, 304 2 of 16 Hence, transformers are subjected to the non-standardized fast transients such as resonant oscillations, which may lead to the dangerous amplification of overvoltages inside the windings [3,13]. Proper transformer grounding should also be not neglected, which in case of lightning, may result in a higher total impedance and can lead to higher transformer terminal voltages than those computed by ideal grounding [14]. The frequency domain view allowed for the determination of the bands in the spectrum prone to resonances. If the incoming transient has a frequency content related to the resonance frequency zone, then the overvoltage amplification inside a winding might occur. Such cases are analyzed in the paper for various classes of the waveforms. The amplification or attenuation of overvoltages are analyzed along the transformer winding and also from the high voltage (HV) winding to low voltage (LV) side transfer perspective. Such tests of voltage exposure and overvoltage propagation allow a check of transformer immunity and are related to both distribution and power units. In the case of power transformers, standards [15–19] also require compliance with tests based on tail chopped lightning impulse. This kind of extended testing is recommended in configurations where the transformer is protected by a spark-gap or is operating in connection to a gas insulated substation. Power transformer units for a grid above 170 kV are checked routinely applying chopped lightning impulse, usually with a time delay to chopping in the range 3 µs and 10 µs [15,16,20]. Presented measurements were conducted both for a full impulse and chopped one, with the time delay to chopping from 1 µs up to 50 µs. Another class of transient stresses is addressed by a rectangular impulse with a variable rise time, reflecting the behavior of power equipment in response to protection devices such as surge arresters. Above tests are complemented by a superimposed configuration of waveform composed of a full lighting impulse with an oscillating component, named a modulated wavelet. Such a waveform might mimic, for example, the oscillating packet appearing at the transformer terminals, propagated by the re-strikes in circuit breakers. According to the design principles, the peak values of transient overvoltages at transformer clamps are constrained by the installed protective devices to the level suggested by the insulation coordination [1,7,21,22]. Those values are much higher than the maximum nominal voltage, thus the incoming transient containing the oscillating component below the protection level may form overvoltages inside the insulation system of high voltage equipment caused by internal resonance in the windings despite the applied surge arresters. Particularly some switching transients, generated in gas insulated substations, during power making or breaking in lines supplying the transformers, ground faults or network reconfigurations, including those originated form power electronics, having oscillating character may cause high amplitude internal overvoltages. The amplitude of the overvoltage depends on the network topology, attenuation conditions and duration of the oscillating components. Transformer windings form a complex distributed resistive-inductive-capacitive (RLC) network, reflecting various internal resonances. Hence, the internal overvoltages recorded along the winding height may vary from the proportionally attenuated incoming external transients [3,23–27]. For this reason, study on internal transient waveforms in transformers, subjected to standard and non-standard excitations, including superimposed waveforms containing oscillating components, are important for the development of more reliable transformers. In this context, the mapping of overvoltage prone zones along the winding length can contribute to the development of proper diagnostic methodology, improved protection concepts and the proper design of modern networks. 2. Characteristic of Voltage Waveforms Applied to Transformer Winding In order to achieve a holistic view of test transformer response to various overvoltages, the following voltage stimulus, graphically illustrated in Table 1, have been applied: (a) (b) (c) (d) full lighting impulse, chopped lighting impulse, rectangular impulse with a variable risetime, modulated wavelet, i.e., superposition of a full lighting impulse with an oscillating component. The lightning impulse waveform Ul can be described by the following double exponential function: function: (1) π (π‘) = π [exp(−π‘/π ) − exp(−π‘/π )] π (π‘) = π [exp(−π‘/π ) − exp(−π‘/π )] (1) (1) ) − magnitude. π (π‘)constant = π [exp(−π‘/π exp(−π‘/π )] For example, in high voltage testing, where τ1 and τ2 define a time and U1 the 1 and τ22 define a time constant and U11 the magnitude. For example, in high voltage testing, where τ 1 for the standard impulse 1.2/50 µsU the time constants correspond to τ1 = 0.405 µs and τ2 = where τ1 and τ2 lightning define a time constant and 1 the magnitude. For example, in high voltage testing, for the lightning impulse 1.2/50 µs the time constants correspond to τ11 = 0.405 µs and τ322 of = 68.2 µs.standard Energies 13, 304 for 2020, the standard lightning impulse 1.2/50 µs the time constants correspond to τ1 = 0.405 µs and τ2 =16 68.2 µs. 68.2 µs. Table 1. Characteristic of voltage waveforms applied to transformer windings. Table1.1.Characteristic Characteristicof of voltage voltage waveforms applied to transformer windings. Table windings. Table 1. Characteristic of voltagewaveforms waveformsapplied applied to to transformer transformer windings. (a) Full lighting impulse (a) Full lighting impulse t(a) f—Front time Fulllighting lighting impulse (a) Full impulse tttfff—Front time tt—Front —Time to half of wave tail time f—Front time ttttt—Time tohalf halfofofwave wave —Time to tailtail tt—Time to half of wave tail (b) Chopped lighting impulse (b) Chopped lighting impulse T(b) c—Time delay to chopping Chopped lighting impulse Chopped lighting impulse T(b) cc —Time delay to chopping c—Collapse time c —Time delay to chopping TtT —Time delay to chopping c ttcc—Collapse time time c—Collapse time ct—Collapse (c) Rectangular impulse with a variable (c) Rectangular impulse with a variable risetime (c) Rectangular impulse with a variable (c) Rectangular impulse with a variable risetime risetime t0—Initial time trisetime —Initial time tt0001—Initial oftime risetime —Initial time t1t0—End —End of risetime ttt11r—End of risetime —Rise time —Rise time rt1—End of risetime trr—Rise time tr—Rise time (d) Superposition of full lighting impulse with (d) Superposition of fulllighting lightingimpulse impulse with oscillating component (d) Superposition ofoffull with (d) Superposition full lighting impulse with oscillating component oscillating component toscillating f—Front time component —Front time tttfff—Front time t—Time to half of wave tail f—Front time tttt—Time to half of wave tail ttt—Time to halfand of wave tail of oscillating ,, ttw2—Initial end time tw1t—Time to half ofend wave tail tw1 and time of oscillating packet w2 —Initial w1, tw2 w2—Initial and end time of oscillating w1 tω packet oscillating packet tww1—Frequency , tw2—Initialofand end time of oscillating packet ωpacket w—Frequency of oscillating packet ωww—Frequency of oscillating packet ωw—Frequency of oscillating packet In order to design the chopped impulse Ucl (Figure 1a), the inverted and shifted lightning Special attention was paid to the propagation of those overvoltages along the high and low In order design the chopped impulse Uclcl (Figure 1a), the inverted and shifted lightning waveform U-lsto is add (Figure 1b): In order to design the chopped impulse U cl (Figure 1a), the inverted and shifted lightning voltage windings as well as to the inter winding transfer case, while applying the stimulus between -ls is add (Figure 1b): waveform U-ls ( ) ( ) U-ls is add (Figure (π‘)1b): πground. ] − exp[ − ] for t ≥ Tc = −π exp[ − the waveform winding terminal and (2) ( ) ( ) (π‘) ( ) − exp[ − ( ) π exp[ − ] ] for = −π t ≥ T (2) c c The lightning impulseπwaveform exponential function: (π‘) = −π Uexp[ l can−be described ] − exp[ −by the] following for t double ≥ Tc (2) π (π‘) = 0 for t < Tc (π‘)==U01 [exp(−t/τ1 ) − exp(−t/τ2 )] for t < Tcc Uππ (1) l (t) (π‘) = 0 for t < Tc Delay of chopping Tc can be tuned in a broad range—in the presented paper, up to 50 µs. In this ofτ chopping cc can be tuned inthe a broad range—in presented paper, up to 50 µs. In this way,Delay a1 and chopped lightning impulse on and on thethe tail is created. collapse time c isfor where τDelay define aT time constant and the magnitude. For example, inThe high voltage testing, of2 chopping be tuned inU a 1front broad range—in the presented paper, up to 50 µs. In tthis Tc can c is way, a chopped lightning impulse on the front and on the tail is created. The collapse time t c tolightning be about 0.1 µs. impulse Thus, lightning impulse the UThe cl_tail,collapse shown way, a chopped lightning the front and oncorrespond the tail on is created. tc isµs. theassumed standard impulse 1.2/50the µsonchopped the time constants to τtail µs and τin =Figure 68.2 1 = 0.405 2time cl_tail, shown in Figure assumed toby bedescribed about 0.1by µs.equation: Thus, the chopped lightning impulse on the tail Ucl_tail 1a, can be assumed be design about 0.1 Thus, theimpulse choppedUlightning impulse oninverted the tail Uand cl_tail, shown Figure In ordertoto theµs.chopped 1a), the shiftedinlightning cl (Figure 1a, can be by described by equation: 1a, can be by equation: waveform U-lsbyisdescribed add (Figure 1b): (3) π _ (π‘) = π (π‘) + π (π‘) (π‘) (π‘) (π‘) (3) π = π + π _ π _ (π‘) = π (π‘) + π (π‘) (3) (t−T ) (t−T ) U−ls (t) = −U2 exp[− τ3 c ] − exp[− τ4 c ] for t ≥ Tc (2) U−ls (t) = 0 for t < Tc Delay of chopping Tc can be tuned in a broad range—in the presented paper, up to 50 µs. In this way, a chopped lightning impulse on the front and on the tail is created. The collapse time tc is assumed to be about 0.1 µs. Thus, the chopped lightning impulse on the tail Ucl_tail , shown in Figure 1a, can be by described by equation: Ucl_tail (t) = Ul (t) + U−ls (t) (3) π (π‘) = −π exp[ − ( ) ο‘ ] sin [ ο·(π‘ − π − π‘ )] for t ≥ Tc + tc π (π‘) = 0 for (6) t < Tc + t c where U4, τα and ω are, respectively, the values of the magnitude, damping time constant and 4 of 16 oscillation frequency. Energies 2020, 13, 304 Figure 1. Illustrative formation of chopped impulse: (a) tail chopped impulse, (b) composition of Figure 1. Illustrative formation of chopped impulse: (a) tail chopped impulse, (b) composition of component pulses for tail chopped impulse, (c) front chopped impulse, (d) composition of component component pulses for tail chopped impulse, (c) front chopped impulse, (d) composition of component pulses for front chopped impulse. pulses for front chopped impulse. To design the impulse chopped on the front before reaching the prospective peak, the additional To illustrate and1d) to isquantify spectralbydensity of full and chopped lightning impulses, the waveform Uh (Figure needed,the described the following equation: frequency analysis was performed (Figure 2), using the above presented methodology. It was based on two time-shifted pulses having inverted to achieve (t−T −t ) voltage waveform with desired front (t−T −tpolarity ) Uh (t) = −U3 exp[− τc5 c ] − exp[− τc6 c ] for t ≥ Tc + tc (4) time and delayed chopping moment. ( ) U t = 0 for t < T + t c c h The chopping time significantly influences the spectral content compared with the full lightning impulse voltage, i.e., the shorter the time to chopping, the spectrum is broader but simultaneously Hence, for chopped lightning impulse on the front Ucl_front , the superposition of full lightning impulse Ul , inverted and shifted one U-ls and additional waveform Uh is performed, as presented in Figure 1c,d and given by the expression: Ucl_ f ront (t) = Ul (t) + U−ls (t) + Uh (t) (5) When decaying oscillations Udh follow the impulse fall at the chopping point, at a time moment t = Tc + tc , the corresponding waveform component may be represented by the following expression: (t−Tc −tc ) ( )] Udh (t) = −U4 exp[− ] sin [ ω t − T − t for t ≥ Tc + tc c c τ Udh (t) = 0 for t < Tc + tc (6) where U4 , τα and ω are, respectively, the values of the magnitude, damping time constant and oscillation frequency. To illustrate and to quantify the spectral density of full and chopped lightning impulses, the frequency analysis was performed (Figure 2), using the above presented methodology. It was based on two time-shifted pulses having inverted polarity to achieve voltage waveform with desired front time and delayed chopping moment. Energies 2020, 13, x FOR PEER REVIEW 5 of 16 the energy spectral density lower. This effect might have a significant implication in the case of internal transients Energies 2020, 13, 304 occurring along windings lengths, while performing chopped and full lightning 5 of 16 probe. Figure Spectral content content of of chopped chopped and and full full lightning Figure 2. 2. Spectral lightning impulse impulse (FLI). (FLI). Delay Delay time time to to chopping chopping respectively: (1) 0.8 µs, (2) 2 µs, (3) 2 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) FLI. respectively: (1) 0.8 µs, (2) 2 µs, (3) 2 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) FLI. The chopping time significantly influences the spectral content compared with the full lightning Another applied waveform was a rectangular impulse with a variable risetime tr calculated impulse voltage, i.e., the shorter the time to chopping, the spectrum is broader but simultaneously the between 10% and 90% of voltage slope magnitude U5. In the presented model, a rectangular impulse energy spectral density lower. This effect might have a significant implication in the case of internal rise time is initiated at time t0 and lasts until time moment t1 with a slope β. Such a waveform can be transients occurring along windings lengths, while performing chopped and full lightning probe. described by the following expression: Another applied waveform was a rectangular impulse with a variable risetime tr calculated πππ π‘ < π‘ 0 between 10% and 90% of voltage slope magnitude U . In the presented model, a rectangular impulse πππ5 π‘ > π‘ πππ π‘ < π‘ π (π‘) = ο’π‘ (7) rise time is initiated at time t0 and lasts until π time moment πππ π‘ >t1π‘ with a slope β. Such a waveform can be described by the following expression: The last case of a stimulus waveform Ulw presented in this paper refers to the superposition of a ο£± component Uw, appearing at time moment tw1 and lasting until full lighting impulse Ul with oscillating  0 f or t < t0   ο£² tw2. Such a waveform with superimposed wavelet can expression: Ur ( t ) =  (7) βt f or be t >represented t0 and t < tby 1   ο£³ U f or t > t 5 π (π‘) = π + π = π + π exp( −(π‘ − π‘ ) /π ) sin [ ο· 1 (π‘ − π‘ )] for tw1 < t < tw2 (8) The(π‘)last case of a stimulusfor waveform Ulw tpresented in this paper refers to the superposition of a π t < tw1 and > tw2 =π full lighting impulse Ul with oscillating component Uw , appearing at time moment tw1 and lasting where τw and ωw are the width and frequency of the oscillating packet. until tw2 . Such a waveform with superimposed wavelet can be represented by expression: 3. Measurement Setup and Test Object Ulw (t) = Ul + Uw = Ul + U6 exp(− t − tw1 )2 /τw sin[ωw (t − tw1 )] for tw1 < t < tw2 (8) The measurement on transformer windings were performed, both time Ulw (t) = Ul for t in < tw1 andand t > tfrequency w2 domain, in a setup presented in Figure 3. The lightning voltage pulses were generated by a lightning where ωwmaximum are the width and frequency of the packet. stroke τunit with amplitude 300 V. The testoscillating waveforms with oscillating component as well w and as the measurements in frequency domain from 20 Hz to 2 MHz were performed using 3. Measurementfunction Setup and Test Object programmable generator Tektronix type AFG310 with maximum output voltage 20 V. It is important to notice thaton the magnitudewindings of the generated voltage waveforms used experiments does The measurement transformer were performed, both in time andinfrequency domain, not have a practical impact on measurement results. The influence of the ferromagnetic transformer in a setup presented in Figure 3. The lightning voltage pulses were generated by a lightning stroke core with in themaximum analysis of transients300 is often subject of discussion. The contentious issueas concerns the unit amplitude V. Thea test waveforms with oscillating component well as the cutoff frequencyinoffrequency transformer core impact. to the investigations by Wilcox measurements domain from 20Usually, Hz to 2referring MHz were performed using done programmable [28], in a generator frequency Tektronix range above several dozens kHz, the impact the core20 is V. neglected. Hence, to in function type AFG310 withofmaximum outputofvoltage It is important this high frequency band, the can be treatedwaveforms as linear objects the magnitudes applied notice that the magnitude of windings the generated voltage used and in experiments doesofnot have stimuli do not influence the measurements. For the acquisition of the overvoltage waveforms, avoltage practical impact on measurement results. The influence of the ferromagnetic transformer core in an oscilloscope Tektronixismodel wasofused as in the configuration in Figure The the analysis of transients often a784D subject discussion. The contentious shown issue concerns the3a. cutoff frequency of characteristics of the windings were obtained in the computer controlled configuration. frequency transformer core impact. Usually, referring to the investigations done by Wilcox [28], in a The generator was programmed to yield the sweep in predefined frequency range (up to 2 MHz) and frequency range above several dozens of kHz, the impact of the core is neglected. Hence, in this high frequency band, the windings can be treated as linear objects and the magnitudes of applied voltage stimuli do not influence the measurements. For the acquisition of the overvoltage waveforms, an Energies 2020, 13, 304 6 of 16 Energies 2020, 13, x FOR PEER REVIEW 6 of 16 oscilloscope Tektronix model 784D was used as in the configuration shown in Figure 3a. The frequency characteristics of the windings were obtained in the computer controlled configuration. The generator the programmed corresponding response was in acquired by frequency an oscilloscope. Both programmable function was to yield the sweep predefined range (up to 2 the MHz) and the corresponding generator and the scope acting as a recorder were linked with a control computer by GPIB-USB. The response was acquired by an oscilloscope. Both the programmable function generator and the scope controlasand analysiswere software was developed incomputer LabView™by environment Nationaland Instruments acting a recorder linked with a control GPIB-USB.from The control analysis [3,10,26,29]. software was developed in LabView™ environment from National Instruments [3,10,26,29]. Figure 3. Measurement setup: (a) time domain measurements of overvoltages along transformer windings, (b) frequency domain and combined waveform measurements. Figure 3. Measurement setup: (a) time domain measurements of overvoltages along transformer windings, (b) frequency domain andpaper combined measurements. All experiments presented in this werewaveform performed on the test transformer 20 kVA 15/0.4 kV. The rated and design parameters of the experimental unit are shown in Table 2. This kind of distribution All experiments presented in thisto paper performed on the test transformer 20 kVA transformer was selected on purpose test awere variety of overvoltage waveforms. Such a unit15/0.4 can kV. The rated and design parameters of the experimental unit are shown in Table 2. This kind of be subjected to both full lightning and chopped lightning stroke as well as to transients containing distribution transformer was selected on purpose to test a variety of overvoltage waveforms. Such a superimposed oscillating component due to switching operations in the network. The systema unit can be subjected to both full lightning and chopped lightning strokeofasconnected well as torenewable transients reconfigurations will occur increasingly frequently in the grid as a result containing and a superimposed oscillating due infrastructure to switching operations in the network. The generation expanding charging andcomponent energy storage for e-mobility. system reconfigurations will occur increasingly frequently in the grid as a result of connected renewable generationTable and 2.expanding charging and energy storage Experimental transformer rated and designinfrastructure parameters. for e-mobility. Parameter Valueparameters. Table 2. Experimental transformer rated and design Sr , (kVA) Parameter UrHV ,S(kV) r, (kVA) UrLV ,U (kV) rHV, (kV) number of electrical phases UrLV, (kV) number Uz , of (%)electrical phases Uz, (%) βPFe , (kW) ΔPFe, (kW) βPk , (kW) ΔPk, (kW) I0 , (%) I0, (%) number of turns in the in coilthe coil number of turns number of coils number of coils winding height l, (mm) winding height l, (mm) internal coil diameter do, (mm) internal coil diameter do , (mm) externat coil diameter di, (mm) externat coil diameter di , (mm) coil width h, (mm) coil width h, (mm) 20 Value 15 20 0.4 15 3 0.4 3 4.2 4.2 0.11 0.11 0.53 0.53 2.8 2.8 810 810 44 280 280 157 157 205 205 25 25 The research was focused on the analysis of overvoltages occurring inside transformer high and The research was focused analysis of overvoltages transformer highwere and low voltage windings as wellon asthe transferred from HV to LVoccurring side. Theinside ground overvoltages low voltage windings as well as transferred from HV to LV side. The ground overvoltages were measured along the HV winding, at tap x/l denoted as follows: x/l = 0 (corresponds to the clamp of the phase L1), x/l = 0.2, x/l = 0.3, x/l = 0.7), applying various stimuli waveforms from the terminal side. The access to the internal winding structure was possible through additional taps installed inside in the winding. Due to the paper limitations, certain characteristic tap positions were selected to the Energies 2020, 13, 304 7 of 16 Energies 2020, 13, x FOR PEER REVIEW 7 of 16 measured along the HV winding, at tap x/l denoted as follows: x/l = 0 (corresponds to the clamp of the phase L1), x/l = 0.2, x/l = 0.3, x/l = 0.7), applying various stimuli waveforms from the terminal side. visualization of the voltage distributions along the windings. For evaluation purposes, both the The access to the internal winding structure was possible through additional taps installed inside frequency and time relationships ko of internal overvoltages in the transformer winding are calculated in the winding. Due to the paper limitations, certain characteristic tap positions were selected to using following expression: the visualization of the voltage distributions along the windings. For evaluation purposes, both the u frequency and time relationships ko of internal overvoltages in the transformer winding are calculated ko = x / l (9) u0- max using following expression: ux/l ko = (9) where: u0− max u x/l—measurement at tap x/l along the winding, where: u0-max—magnitude of external stimulus applied at winding clamps (tap x/l = 0 and x/l = 1.0). ux/l —measurement at tap x/l along the winding, The distributions of maximum internal winding overvoltages ko-max is obtained according to the u0- max —magnitude of external stimulus applied at winding clamps (tap x/l = 0 and x/l = 1.0). relationship: The distributions of maximum internal winding overvoltages ko- max is obtained according to ux / l max − = k (10) the relationship: o− max uux/l 0- max − max ko− max = (10) u0− max where: u x/—lmaximum value obtained for measurement at tap x/l along the winding, where: u0-max—highest magnitude of external stimulus applied at winding clamps (tap x/l = 0 and x/l = ux/ l —maximum value obtained for measurement at tap x/l along the winding, 1.0). u0- max —highest magnitude of external stimulus applied at winding clamps (tap x/l = 0 and x/l = 1.0). 4. Overvoltages in Frequency Domain 4. Overvoltages in Frequency Domain Determination of the winding broadband characteristics in a frequency domain allows the Determination of the winding broadband characteristics in a frequency domain allows the determination of sensitive zones and resonance frequencies [3,10,12,29]. It is well suited for analysis determination of sensitive zones and resonance frequencies [3,10,12,29]. It is well suited for analysis of of the response of a transformer winding to an excitation in form of an oscillating packet of the response of a transformer winding to an excitation in form of an oscillating packet of overvoltage overvoltage occurring in an electrical network. The normalized frequency characteristics of occurring in an electrical network. The normalized frequency characteristics of overvoltages along the overvoltages along the windings are presented in Figure 4. Depending on the excitation spectral windings are presented in Figure 4. Depending on the excitation spectral content match with these content match with these characteristics, the stress on electrical insulation systems is obtained. From characteristics, the stress on electrical insulation systems is obtained. From the plot one can notice the plot one can notice characteristic frequencies, for which sinusoidal excitations are strongly characteristic frequencies, for which sinusoidal excitations are strongly amplified inside the winding. amplified inside the winding. Those frequencies may fit with spectrum of incoming external Those frequencies may fit with spectrum of incoming external overvoltages. For example (Figure 4), overvoltages. For example (Figure 4), the overvoltage ratio in case of HV winding at frequency 12 the overvoltage ratio in case of HV winding at frequency 12 kHz equals to 3.4 p.u. Analysis confirms, kHz equals to 3.4 p.u. Analysis confirms, that excitation waveforms having oscillating wavelet may that excitation waveforms having oscillating wavelet may undergo amplification inside transformer undergo amplification inside transformer winding because of resonance phenomena, especially if the winding because of resonance phenomena, especially if the frequencies of the applied voltage are frequencies of the applied voltage are matching the self frequencies of the transformer winding. matching the self frequencies of the transformer winding. Figure 4. 4. Frequency Frequency characteristic characteristic of of terminal terminal overvoltages overvoltages and and for for point point in in half half of of windings windings and and Figure ground: (a)—HV windings, (b)—LV windings. ground: (a)—HV windings, (b)—LV windings. From the frequency characteristics of overvoltages in HV and LV experimental transformer From the frequency characteristics of overvoltages in HV and LV experimental transformer windings (Figure 4), one can notice, that sinusoidal voltages at resonance frequencies propagated in windings (Figure 4), one can notice, that sinusoidal voltages at resonance frequencies propagated in transformer undergo amplification inside the windings. For example, in HV windings oscillating overvoltages reach maximum for following frequencies 0.65 kHz, 13.1 kHz, 36.7 kHz and 51 kHz and in LV windings for frequencies: 0.64 kHz, 8.7 kHz, 107 kHz and 0.85 MHz. If the resonant frequencies Energies 2020, 13, 304 8 of 16 Energies 2020, 13, x FOR PEER REVIEW 8 of 16 transformer undergo amplification inside the windings. For example, in HV windings oscillating Energies 2020, 13, x FOR PEER REVIEW 8 ofin16 overvoltages reach maximum for following frequencies 0.65 kHz, 13.1 kHz, 36.7 kHz and 51 kHz and of the transformer is larger, then the probability of multiplication of internal overvoltages in LV windings for frequencies: 0.64 kHz, 8.7 kHz, 107 kHz and 0.85 MHz. If the resonant frequencies of transformers is greater. It was also observed that maximal values of oscillating in of transformer the transformer is larger, the probability of multiplication of internal overvoltages overvoltages the is larger, then thethen probability of multiplication of internal overvoltages in transformersin windings occurs, practically for the same frequencies, for all phases. is also greater. It wasthat also observed that of maximal values of oscillating overvoltages in istransformers greater. It was observed maximal values oscillating overvoltages in windings occurs, In turn, an interesting case is a transfer characteristic i.e., stimuli on HV winding side and windings for occurs, practically for thefor same for all phases. practically the same frequencies, all frequencies, phases. response measured at LV winding, as presented in Figure 5. i.e., Illustration of to LV transfer In turn, an interesting case is a transfer characteristic on the HVHV winding side and In turn, an interesting case is a transfer characteristic i.e., stimuli stimuli on HV winding side and response characteristic of overvoltages for injecting the signal at HV terminal of phase A and recording response at measured at LV winding, as presented in Figure of 5. the Illustration the HV to LV transfer measured LV winding, as presented in Figure 5. Illustration HV to LVof transfer characteristic of response at LV of winding phase “a” isinjecting shown inthe Figure 5a,atwhile an analogous case reflecting HV-LV characteristic overvoltages for signal HV terminal of phase A and overvoltages for injecting the signal at HV terminal of phase A and recording response at LV recording winding winding phase is shown in Figure 5b. response LVC-c winding phase “a” isan shown in Figure while an analogous case reflecting HV-LV phase “a” isatshown in Figure 5a, while analogous case 5a, reflecting HV-LV winding phase C-c is shown phase C-c is shown in Figure 5b. inwinding Figure 5b. (a) (b) (a) (b) (x = 1.00) and for point Figure 5. Transfer frequency characteristic of overvoltages at winding terminal in half of windingsfrequency and ground (x = 0.50): of (a) injection HVatwindings phase A,(xresponse LV for winding Figure Figure5.5.Transfer Transfer frequencycharacteristic characteristic ofovervoltages overvoltages atwinding windingterminal terminal (x= =1.00) 1.00)and and forpoint point phase “a”, (b) injection HV winding phase C, response LV winding phase “c”. ininhalf halfofofwindings windingsand andground ground(x(x==0.50): 0.50):(a) (a)injection injectionHV HVwindings windingsphase phaseA, A,response responseLV LVwinding winding phase phase “c”. phase“a”, “a”,(b) (b)injection injectionHV HVwinding windingphase phaseC,C,response responseLV LVwinding winding phase “c”. 5. Propagation of Different Waveforms in Transformer Windings in Time Domain 5. Propagation of Different Waveforms in Transformer Windings in Time Domain 5. Propagation ofrecorded DifferentinWaveforms in of Transformer Windings Domain Overvoltages various parts a transformer windingin inTime response to different stimuli Overvoltages recorded in various parts of a transformer winding in response stimuli waveforms are presented in this section.parts of a transformer winding in responsetotodifferent Overvoltages recorded in various different stimuli waveforms are presented in this section. waveforms are presented in this section. 5.1. Full Lightning Voltage Impulse 5.1. Full Lightning Voltage Impulse 5.1. Overvoltages Full Lightning measured Voltage Impulse between selected points x/l of both HV and LV winding and ground Overvoltages measured between selected points x/linofFigure both HV LV winding and ground duringOvervoltages the full lightning impulse u0(t) are presented 6a,and whereas the corresponding measured between selected points x/l of both HV and LV winding and ground during the full lightning impulse u0shown (t) are presented in Figure 6a, whereas the corresponding differences differences of inter taps ratios are in Figure 6b. The magnitude of the waveform is normalized during the full lightning impulse u0(t) are presented in Figure 6a, whereas the corresponding of inter taps ratios are shown in Figure 6b. The magnitude of the waveform is normalized with respect with respect of tointer maximal value are of the full in lightning impulse accordingof tothe formula (9). The response differences taps ratios shown Figure 6b. The magnitude waveform is normalized to maximal value of overvoltages the full lightning impulse according to formula (9). The response shapes internal shapes of internal arethe different comparing to the excitation applied at The theofexternal with respect to maximal value of full lightning impulse according to formula (9). response overvoltages are different comparing to the excitation applied at the external transformer clamps of one transformer clamps of one phase. For the tap x/lexcitation = 0.3 in theapplied HV winding, can shapes of internal overvoltages are example, different taking comparing to atthe at the one external phase. For example, taking the tap at x/l = 0.3 in the HV winding, one can recalculate the magnitude of recalculate the magnitude of corresponding lightning impulse, which results in 1.04 p.u, and exceeds transformer clamps of one phase. For example, taking the tap at x/l = 0.3 in the HV winding, one can corresponding lightning which results in 1.04 p.u, and exceeds the impulse peak value. the impulse the peak value. impulse, recalculate magnitude of corresponding lightning impulse, which results in 1.04 p.u, and exceeds the impulse peak value. (a) (b) (a) of (b) (a)(a) HV winding: (1)(1) x/l x/l = 0, x/l = (3) x/l 0.3, Figure 6. Measurement Measurement ofovervoltages overvoltagesatattap tapx/lx/linin HV winding: = (2) 0, (2) x/l0.2, = 0.2, (3)=x/l = (4) 0.7= and (b) corresponding overvoltage differences: 1—u , 2—u , 3—u . 0.3,x/l (4)=x/l 0.7 and (b) corresponding overvoltage differences: 1—u 0-0.2 , 2—u 0.2-0.3 , 3—u 0.3-0.7 . 0-0.2 0.3-0.7 Figure 6. Measurement of overvoltages at tap x/l in (a) HV winding: (1) 0.2-0.3 x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (b) corresponding overvoltage differences: 1—u 0-0.2, 2—u 0.2-0.3, 3—u 0.3-0.7. Energies 2020, 13, 304 9 of 16 5.2. Chopped Lightning Voltage Impulse Energies 2020, 13, x FOR PEER REVIEW 9 of 16 Overvoltages recorded in HV winding of 20 kVA transformer, excited by a lightning voltage 5.2. Chopped Lightning Voltage Impulse impulse, were performed in a broad chopping time delay scope. The lightning impulse was chopped Overvoltages in The HV winding of 20 kVA transformer, excited bytaps a lightning after time tu from 1 µs uprecorded to 50 µs. waveforms measured at selected x/l in avoltage HV winding in impulse, were performed in a broad chopping time delay scope. The lightning impulse was chopped response to the tail chopped lightning voltage impulse, with various chopping time delays: 2 µs, 5 µs, after time tu from 1 µs up to 50 µs. The waveforms measured at selected taps x/l in a HV winding in Energies 2020, 13,in x FOR PEER 7A REVIEW corresponding overvoltage differences in Figure 7B. 9 of 16 maximal and 10 µs, are shown response to the Figure tail choppedand lightning voltage impulse, with various chopping time delays: 2 µs,The 5 µs, and 10 overvoltages µs, are shown inobtained Figure 7A and correspondingat overvoltage differences in Figure 7B. The values of chopped in transformer selected taps x/l depend on time delay to 5.2. Chopped Lightning Voltage Impulse values of chopped overvoltages obtained in transformer at selected taps x/l depend on time chopping tmaximal u . Increased time tu leads to amplification of inter-winding overvoltages. Thus, time delay in HV winding kVA transformer, excited by overvoltages. a lightning voltage delayOvervoltages to chopping recorded tu. Increased time tu leadsofto20 amplification of inter-winding Thus, tu has largetime influence on longitudinal overvoltage can be highlighted especially in a impulse, were performed in a broad timeenhancement. delay scope.enhancement. The In lightning impulse chopped delay tu has large influence onchopping longitudinal overvoltage In can bewas highlighted winding region being a1 µs proximity toThe the after time tin u from up to 50being µs. at selected taps x/l in a HV winding in especially a in winding region in waveforms a transformer proximity measured to theterminals. transformer terminals. response to the tail chopped lightning voltage impulse, with various chopping time delays: 2 µs, 5 µs, and 10 µs, are shown in Figure 7A and corresponding overvoltage differences in Figure 7B. The maximal values of chopped overvoltages obtained in transformer at selected taps x/l depend on time delay to chopping tu. Increased time tu leads to amplification of inter-winding overvoltages. Thus, time delay tu has large influence on longitudinal overvoltage enhancement. In can be highlighted especially in a winding region being in a proximity to the transformer terminals. (A) (B) Figure 7. Measurement of overvoltages applying tail lightning impulse (A) in HV(A) winding Figure 7. Measurement of overvoltages applying tailchopped chopped lightning impulse in HV winding at tap (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (B) corresponding overvoltage differences: at tap (1) x/l = 0, (2) x/l = 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (B) corresponding overvoltage differences: (1) u 0-0.2, (2) u 0.2-0.3, (3) u 0.3-0.7. Time delay to chopping tu: (a) 2 µs, (b) 5 µs, (c) 10 µs. (1) u 0-0.2 , (2) u 0.2-0.3 , (3) u 0.3-0.7 . Time delay to chopping tu : (a) 2 µs, (b) 5 µs, (c) 10 µs. The above measurements lead to the plot shown in Figure 8 representing overvoltages ko-max = (A) and ground as well as gradients of overvoltages (B) f(x/l) between selected points in HV winding kofo-max = f(x/l) The above measurements lead to the plot shown in Figure 8 representing overvoltages transformer excited by both full and chopped lightning voltage impulse employing time delay of tu in Figure 7. Measurement of overvoltages tail chopped lightning impulsein (A)HV in HV winding between selected points and ground as well applying as gradients of overvoltages winding transformer the range upx/l to=50 µs. at tapfrom (1) x/l1=µs 0, (2) 0.2, (3) x/l = 0.3, (4) x/l = 0.7 and (B) corresponding overvoltage differences: excited by both(1)full and chopped lightning voltage impulse employing time delay t in the range from u u 0-0.2, (2) u 0.2-0.3, (3) u 0.3-0.7. Time delay to chopping tu: (a) 2 µs, (b) 5 µs, (c) 10 µs. 1 µs up to 50 µs. The above measurements lead to thetoplot in Figure winding 8 representing overvoltages ko-maxto = Figure 8b The chopped voltage impulse applied theshown transformer results according f(x/l) between selected points and ground as well as gradients of overvoltages in HV winding of in the enhanced gradients, stressing the winding electrical insulation system, especially in a proximity transformer excited by both full and chopped lightning voltage impulse employing time delay tu in to the transformer clamps the range from 1 µs [6,7]. up to 50 µs. Figure 8. (a) Maximal values of overvoltages and (b) overvoltage gradient for full (FLI) and chopped lightning impulse, with time to chopping: (1) 1 µs, (2) 2 µs, (3) 4 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) 30 µs, (8) 50 µs, (9) FLI. lightning impulse, with time to chopping: (1) 1 µs, (2) 2 µs, (3) 4 µs, (4) 6 µs, (5) 10 µs, (6) 20 µs, (7) 30 µs, (8) 50 µs, (9) FLI. The chopped voltage impulse applied to the transformer winding results according to Figure 8b Energies 13, 304 gradients, stressing the winding electrical insulation system, especially10in of 16 in the 2020, enhanced a proximity to the transformer clamps [6,7]. 5.3. Rectangular Rectangular Voltage Voltage Impulse Impulse 5.3. In this this part, measured in in the winding, excited excited by by aa rectangular In part, transients transients measured the transformer transformer winding, rectangular impulse impulse applied at HV clamp (tap x/l = 0 and x/l = 1.0) are presented in Figure 9. applied at HV clamp (tap x/l = 0 and x/l = 1.0) are presented in Figure 9. Figure 9. Overvoltages excited excited by by rectangular rectangular impulse impulse in in the 0, (2) Figure 9. Overvoltages the HV HV winding winding at at tap: tap: (1) (1) x/l x/l = = 0, (2) x/l x/l = = 0.2, (3) x/l = 0.3, (4) x/l = 0.7. 0.2, (3) x/l = 0.3, (4) x/l = 0.7. Overvoltages generated inside the windings contain oscillatory components with a resonance frequency equal to 13.1 kHz. The magnitude manifests great variability, i.e., overvoltages measured at Overvoltages generated the windings containcomparing oscillatorytocomponents resonance tap x/l = 0.3 along the windinginside are roughly 1.3 amplified the impulse with crest avalue at the frequency equal to 13.1 kHz. The magnitude manifests great variability, i.e., overvoltages measured transformer clamp. Due to the relatively low self frequencies of HV windings, overvoltages are not at tap x/l to = 0.3 theof winding are roughly amplified to the impulse value at sensitive the along rise time the applied impulse,1.3 ranging from comparing 10 ns to several hundred ofcrest nanoseconds. the transformer clamp. Due to the relatively low self frequencies of HV windings, overvoltages are In turn, overvoltages generated inside the LV transformer windings in response to the rectangular not sensitive to the rise time of the applied ranging from 10 to nsnotice, to several hundredthe of voltage impulse strongly depend on rise timeimpulse, (Figure 10). It is possible for example, nanoseconds. In turn, overvoltages generated inside the LV transformer windings in response to the overvoltage coefficient kiLV for voltage U0.5c in the LV winding of phase “c” for a rise time of 10 ns is rectangular impulse strongly depend on rise time (Figure 10). Itk is possible to notice, for about 3.3 butvoltage for a rise time 100 ns is about 1.6. The overvoltage coefficient iLV of transient voltage Ua example, the overvoltage coefficient k iLV for voltage U0.5c in the LV winding of phase “c” for a rise time at the terminal of phase “a” for rise time 10 ns reach about 1.95 but for rise time of 100 ns is equal only of to 10 0.7.ns is about 3.3 but for a rise time 100 ns is about 1.6. The overvoltage coefficient kiLV of transient voltage Ua at the terminal of phase “a” for rise time 10 ns reach about 1.95 but for rise time of 100 ns is equal only to 0.7. Figure 10. Overvoltages measured in transformer LV windings in response. to rectangular voltage impulse with different rise times: (a) 10 ns, (b) 100 ns. Figure 10. Overvoltages measured in transformer LV windings in response. to rectangular voltage 5.4. Lightning Voltage Impulse with Superimposed Oscilating Wavelet impulse with different rise times: (a) 10 ns, (b) 100 ns. Another class of stimulus is created by superimposed waveforms. Such an approach allows 5.4. Lightning Voltage Impulse with Superimposed Wavelet winding, which result from the analysis of the internal overvoltages generatedOscilating in the transformer resonance phenomenon at impulse voltagebywith superimposed oscillating component, in theallows form Another class of stimulus is created superimposed waveforms. Such an approach of a wavelet. the resultant waveform contains aperiodic part as a lightning voltage surge analysis of theThus internal overvoltages generated in theantransformer winding, which result from the and an oscillating wavelet. The oscillating frequency of the wavelet has been adjusted to the winding resonance frequencies obtained from frequency characteristics presented in Figure 4. An exemplary case of HV winding response to a lightning voltage impulse with superimposed oscillating wavelet tuned to 8.3 kHz, 13.1 kHz and 108 kHz is shown in Figure 11. One may notice the amplification of the oscillating components related to winding resonance frequencies (8.3 kHz and 13.1 kHz) inside the winding. Simultaneously overvoltages in HV windings have greater values than those generated resonance frequencies obtained from frequency characteristics presented in Figure 4. An exemplary case of HV winding response to a lightning voltage impulse with superimposed oscillating wavelet tuned to 8.3 kHz, 13.1 kHz and 108 kHz is shown in Figure 11. One may notice the amplification of the oscillating components related to winding resonance frequencies (8.3 kHz and 13.1 kHz) inside Energies 2020, 13, 304 11 of 16 the winding. Simultaneously overvoltages in HV windings have greater values than those generated during action just of the lightning impulse. However, overvoltages shown in Figure 11c, excited by duringimpulse action justcontaining of the lightning impulse. However, overvoltages shown in Figure 11c, excited the the lightning oscillating component with frequency 108 kHz are notbyamplified in lightning impulse containing oscillating component with frequency 108 kHz are not amplified in the the LV winding. The wavelet frequency in this case is not matching the sharp winding resonance LV winding. The wavelet frequency in this case is not matching the sharp winding resonance peak at peak at 107 kHz. 107 kHz. Figure 11. Response of the HV windings to lightning impulse containing oscillating components with frequency: (a) 8.3 kHz,HV (b) 13.1 kHz, (c)to 108 kHz. Figure 11. Response of the windings lightning impulse containing oscillating components with frequency: (a) 8.3 kHz, (b) 13.1 kHz, (c) 108 kHz. Similar measurement have been performed on LV winding, adjusting the wavelet frequency to the resonances in frequency characteristic (Figure 4), i.e., 107 kHz, 0.85 MHz. The results presented Similar measurement havestrong been amplification performed of onthe LVoscillating winding, adjusting in the frequency to in Figure 12 also indicated overvoltages LVwavelet windings, for example in in the case of frequency 0.85 MHz, the overvoltage voltage U0.5c is equal to 3.4 the resonances frequency characteristic (Figure 4), i.e., coefficient 107 kHz,for 0.85 MHz. The results presented and for voltage U is about 1.5. Analyzing the de-tuned case, overvoltages generated in HV winding a in Figure 12 also indicated strong amplification of the oscillating overvoltages in LV windings, for excited by the lightning impulse containing oscillating wavelet having frequency 14.6 kHz (Figure 12c) example in the case of frequency 0.85 MHz, the overvoltage coefficient for voltage U0.5c is equal to 3.4 are significantly smaller than for cases of resonance frequencies. and for voltage Ua is about 1.5. Analyzing the de-tuned case, overvoltages generated in HV winding excited by the lightning impulse containing oscillating wavelet having frequency 14.6 kHz (Figure 12c) are significantly smaller than for cases of resonance frequencies. Energies 2020, 13, 304 12 of 16 Energies 2020, 13, x FOR PEER REVIEW 12 of 16 Figure 12. Response of the LV windings to lightning impulse containing oscillating wavelet. with Figure 12. Response of the LV windings to lightning impulse containing oscillating wavelet. with frequency: (a) 107 kHz, (b) 0.85 MHz (c) 14.6 kHz. frequency: (a) 107 kHz, (b) 0.85 MHz (c) 14.6 kHz. 6. Assessment of Overvoltages in Transformer Windings 6. Assessment of Overvoltages in Transformer Windings The various applied excitation have different frequency ranges, both narrow- and broad-band. Thus observedapplied transient overvoltages different responses, applying testing and voltages and The various excitation havemanifest different frequency ranges, both narrowbroad-band. waveforms, which might occur during transformer operation in a network. As a reference of transformer Thus observed transient overvoltages manifest different responses, applying testing voltages and testing, the full lightning impulse was accepted. Poweroperation grid transients reflected waveforms, which might occur during transformer in awere network. Asbyaswitching reference of and oscillating waveforms. Both cases revealed relevant distinctions of maximum overvoltages along transformer testing, the full lightning impulse was accepted. Power grid transients were reflected by the winding. As an assessment factor the Time Domain Severity Factor (TDSF) was used. The TDSF is switching and oscillating waveforms. Both cases revealed relevant distinctions of maximum evaluated according to the following expression [21,22]: overvoltages along the winding. As an assessment factor the Time Domain Severity Factor (TDSF) was Ux/l max used. The TDSF is evaluated according to the following expression [21,22]: TDSF = where: Ux/l maxtest U TDSF= x / l max Ux / l maxtest (11) (11) Ux/lmax —highest magnitude of overvoltages occurring at tap x/l during network operation, where: U —highest magnitude overvoltages occurringatattap tapx/lx/lduring excitednetwork by reference voltage impulse. Ux/lmax x/l maxtest —highest magnitude of of overvoltages occurring operation, Ux/l max test—highest magnitude of overvoltages occurring at tap x/l excited by reference voltage impulse. The TDSF obtained for the experimental transformer was evaluated taking the maximum values of overvoltages yielded by testing with the standard full lightning impulse with crest value Utest = 95 kV [15]. The protection of the unit in a grid operation was considered, assuming two models of surge arresters, having different tripping and time to disconnection parameters. In the first case, the Energies 2020, 13, 304 13 of 16 The TDSF obtained for the experimental transformer was evaluated taking the maximum values of overvoltages yielded by testing with the standard full lightning impulse with crest value Utest = 95 kV [15]. The protection of the unit in a grid operation was considered, assuming two models of surge arresters, having different tripping and time to disconnection parameters. In the first case, the transformer has been protected 12ofkV, Energies 2020, 13, x FOR PEER REVIEWby a surge arrester model SA1 rated for continuous voltage Uc =13 16 whereas the latter one is protected by model SA2 working at Uc = 18 kV. Both surge arresters are applied in the distinctive network operating modes, i.e., SA1 in 15 kV topologies with automatic disconnection of short circuits current to ground, whilst the model SA2 refers to the networks without automatic ground fault clearing clearing [21,22,30]. [21,22,30]. The Therated ratedsurge surgearrester arrester parameters parameters are following: for for SA1 SA1 lightning protection level is U Ulplp == 42 sp = 42 kV kV and and switching one is Usp =31.1 31.1kV kVand and for for SA2 SA2 respectively Ulplp ==63 63kV kVand and U Uspsp==46.7 46.7kV kV[30]. [30].The Thedependencies, dependencies,of ofthe theassessment assessment factor factor TDSF TDSF == f(x/l) f(x/l) for for HV winding of experimental experimental transformer transformer rated rated 20 20 kVA kVA 15/0.4 kV, were calculated and are illustrated in Figure 13. Figure 13. 13. Assessment Assessment factor factor TDSF TDSF ==f(x/l) f(x/l)for forHV HVwinding winding excited excited by by standard standard full full lightning lightning impulse impulse Figure U = 95 kV of experimental transformer protected by two models of surge arresters: (a) U 12 kV kV c test Utest = 95 kV of experimental transformer protected by two models of surge arresters: (a) Uc == 12 (SA1), (b) U = 18 kV (SA2); 1—standard full lightning impulse, 2—sinusoidal wavelet with resonance c (SA1), (b) Uc = 18 kV (SA2); 1—standard full lightning impulse, 2—sinusoidal wavelet with resonance frequency 13.1 13.1 kHz, kHz, 3—rectangular frequency 3—rectangular impulse. impulse. The tabular summary of results of maximum overvoltages obtained for test transformer exposed to The tabular summary of results of maximum overvoltages obtained for test transformer exposed various stresses is presented in Table 3. One can notice, that overvoltages recorded at internal winding to various stresses is presented in Table 3. One can notice, that overvoltages recorded at internal taps of transformer, in certain waveform cases, surpass magnitudes obtained at standard lightning winding taps of transformer, in certain waveform cases, surpass magnitudes obtained at standard voltage impulse tests. Maximum internal overvoltages are recorded for a sinusoidal oscillating lightning voltage impulse tests. Maximum internal overvoltages are recorded for a sinusoidal component with the frequency matching the resonant frequency of transformer. For example, at the oscillating component with the frequency matching the resonant frequency of transformer. For winding tap x/l = 0.7, the response to excitation of 95 kV standard lightning voltage impulse test equals example, at the winding tap x/l = 0.7, the response to excitation of 95 kV standard lightning voltage to 84.6 kV. impulse test equals to 84.6 kV. A comparison of both cases of installed protective devices SA1 and SA2 provide quantitative illustration transientofovervoltage effects.waveforms In the case of a network equipped with SA1, Table 3.of Comparison an impact of various on overvoltages in transformer windings. with an automatic restoration after ground fault occurrence and transient excitation in the form Reference Test the wavelet having the oscillating frequency 13.1 kHz Overvoltages (matching oneinof the transformer winding Network Operation Overvoltages resonance frequencies), the measured overvoltage at the same tap was 102.6 kV. While for the Rectangular Sinusoidal Oscillating experimental connected to a network Windingtransformer Lightning Impulse 95 kV without automatic restoration after a ground fault Impulse Component occurrence, with SA2 device, the overvoltage at tap x/l = 0.7, in the response to excitation Positionprotected x/l duration: Tens of duration: Milliseconds Microseconds (kV) Network with Automatic Fault Clearing (SA1 Uc = 12 kV) Energies 2020, 13, 304 14 of 16 containing the same wavelet with transformer resonant frequency, is equal to 154.1 kV. Such an analysis reflects the transformer winding sensitive zones with respect to waveform frequency content. As an extension of the presented work, further investigations on transformers with different winding topologies and voltage levels are planned. Such an approach could lead to scalable and more general methodology for assessment of overvoltages representing impulse, chopped and oscillating waveforms. Table 3. Comparison of an impact of various waveforms on overvoltages in transformer windings. Reference Test Overvoltages Winding Position x/l Lightning Impulse 95 kV Overvoltages in Network Operation Rectangular Impulse duration: Tens of Microseconds Sinusoidal Oscillating Component duration: Milliseconds (kV) Network with Automatic Fault Clearing (SA1 Uc = 12 kV) 0 0.18 0.33 0.67 95.0 95.0 102.6 84.6 42.0 53.3 59.2 45.4 31.1 48.2 78.4 102.6 Network without Automatic Fault Clearing (SA2 Uc = 18 kV) 0 0.18 0.33 0.67 95.0 95.0 102.6 84.6 63.0 80.0 88.8 68.0 46.7 72.4 117.7 154.1 7. Conclusions This paper reports about propagation of various waveforms of overvoltages inside transformer winding stressing the electric insulation system. Especially highlighted are overvoltage exposures in response to a lightning voltage impulse, rectangular one and impulse containing sinusoidal oscillating component. The experiments were performed on a distribution transformer, which can be subjected in real operating conditions to such stresses in an electric network. The transformer insulation between windings and ground is exposed to the largest maximal of overvoltages during the tests with full lightning voltage impulses. The application of chopped lightning impulses, with a variable delay time to chopping does not increase the recorded transients. However, chopped lightning voltage impulses result in an enhancement of the overvoltage gradients in the electrical insulation, especially localized close to the transformer clamps. It was observed that excitation with the lightning voltage impulses chopped on tail, with a delay time above 6 µs, does not cause an increase of overvoltage impact in experimental winding. It was noticed that attention should be paid to overvoltages containing oscillating component, especially those having the frequency close to one of the winding resonance frequencies. Knowledge of these effects broadens the knowledge about transformer immunity tests and recommendations for new designs, resistant to new classes of transients and overvoltages occurring in resilient power grid. Author Contributions: All authors cooperated fully and equally at all stages of the presented research and during the preparation of the article. All authors have read and agreed to the published version of the manuscript. Funding: This research received no external funding. Conflicts of Interest: The authors declare no conflict of interest. References 1. 2. Joint Working Group A2/C4.39-CIGRE. Electrical Transient Interaction between Transformers and the Power System (Part 1-Expertise, Part 2: Case Studies); CIGRE: Paris, France, 2014. Massaro, U.; Antunes, R. Electrical transient interaction between transformers and power system–Brazilian experience. In International Conference on Power Systems Transients (IPST2009); Publisher: Kyoto, Japan, 2009; pp. 1–6. Energies 2020, 13, 304 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 15 of 16 Florkowski, M.; FurgaΕ, J. High Frequency Methods for Condition Assessment of Transformers and Electrical Machines; Publishing House AGH: Kraków, Poland, 2013; ISBN 978-83-7464-614-7. Rocha, C.A.O. Electrical Transient Interaction between Transformers and the Power System; CIGRE-Brazil Joint Working Group JWG–A2/C4-03: Paris, France, 2008; pp. 1–6. Hori, M.; Nishioka, M.; Ikeda, Y.; Naguchi, K.; Kajimura, K.; Motoyama, H.; Kawamura, T. Internal winding failure due to resonance overvoltages in distribution transformer caused by winter lightning. IEEE Trans. Power Deliv. 2006, 23, 1600–1606. Lapworth, J.A.; Wilson, A. Transformer internal overvoltages caused by remote energization. In Proceedings of the 2007 IEEE Power Engineering Society Conference and Exposition in Africa-PowerAfrica, Johannesburg, South Africa, 16–20 July 2007; pp. 1–6. FurgaΕ, J. Analysis of overvoltages in windings of power transformers protected by use of metal oxide surge arresters. Eur. Trans. Electr. Power Eng. 2009, 19, 400–410. [CrossRef] Shipp, D.D.; Dionise, T.J.; Lorch, V.; MacFarlane, B.G. Transformer failure due to circuit-breaker-induced switching transients. IEEE Trans. Ind. Appl. 2011, 47, 707–718. [CrossRef] Holdyk, A.; Gustavsen, B. External and internal overvoltages in a 100 MVA transformer during high-frequency transients. In Proceedings of the International Conference on Power System Transmission (IPST), Cavtat, Croatia, 15–18 June 2015; pp. 1–6. Florkowski, M.; FurgaΕ, J.; Kuniewski, M.; Pajak, Λ P. Comparison of transformer winding responses to standard lightning impulses and operational overvoltages. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 965–974. [CrossRef] Srikanta Murthy, A.; Azis, N.; Mohd Yousof, M.F.; Jasni, J.; Othman, M.L.; Talib, M.A.; Das, B.P. Investigation on the Resonant Oscillations in an 11 kV Distribution Transformer under Standard and Chopped Lightning Impulse Overvoltages with Different Shield Placement Configurations. Energies 2019, 12, 1466. [CrossRef] Zhang, Z.; Gao, W.; Kari, T.; Lin, H. Identification of Power Transformer Winding Fault Types by a Hierarchical Dimension Reduction Classifier. Energies 2018, 11, 2434. [CrossRef] Popov, M. General Approach for accurate resonance analysis in the transformer. Electr. Power Syst. Res. 2018, 161, 45–61. [CrossRef] Popov, M.; Grcev, L.; Hoidalen, H.K.; Gustavsen, B.; Terzija, V. Investigation of the Overvoltage and Fast Transient Phenomena on Transformer Terminals by Taking into Account the Grounding Effects. IEEE Trans. Ind. Appl. 2015, 51, 5218–5227. [CrossRef] IEC 60076-3 Power Transformers–Part 3: Insulation Levels. Dielectric Tests and External Clearances in Air. Available online: https://webstore.iec.ch/publication/62880 (accessed on 8 November 2019). IEEE C57.98 Guide for Transformer Impulse Tests. IEEE Power Energy Soc. 2012. [CrossRef] Neto, E.T.W.; Lopes, G.P.; Martinez, M.L.B.; Salles, C. Chopped impulses for distribution transformers their importance for dimensioning and performance evaluation. In Proceedings of the 2014 International Conference on Lightning Protection (ICLP), Shanghai, China, 11–18 October 2014; pp. 473–478. Bhuyan, K.; Chatterjee, S. Electric stresses on transformer winding insulation under standard and non-standard impulse voltages. Electr. Power Syst. Res. 2015, 123, 40–47. [CrossRef] Florkowski, M.; FurgaΕ, J.; Kuniewski, M. Propagation of overvoltages transferred through distribution transformers in electric networks. IET Gen. Trans. Distr. 2016, 10, 2531–2537. [CrossRef] Munshi, S.; Roy, C.K.; Biswas, J.R. Computer studies of the performance of transformer windings against chopped impulse voltages. IEE Proc. C 1992, 139, 286–294. [CrossRef] Standard EN 60071-1 Coordination of Insulation. Definitions, Principles and Rules. Available online: https://webstore.iec.ch/publication/65606 (accessed on 8 November 2019). Standard EN 60099-5 Surge Arresters. Recommendation of Selection and Use. Available online: https: //webstore.iec.ch/publication/736 (accessed on 8 November 2019). Lopez-Fernandez, X.M.; Álvarez-Mariño, C. Induced transient voltage performance between transformers and VCB-severity factors and case studies. IEEE Trans. Power Deliv. 2015, 30, 1137–1144. [CrossRef] Florkowski, M.; FurgaΕ, J.; Kuniewski, M.; Pajak, Λ P. Investigations of transformer winding response to standard full and chopped lightning impulses. In Proceedings of the 2018 IEEE International Conference on High Voltage Engineering and Application (ICHVE), Athens, Greece, 10–13 September 2018. Rodrigues, R.B.; Mendes, V.M.F.; Catalão, J.P.S. Analysis of Transient Phenomena Due to a Direct Lightning Strike on a Wind Energy System. Energies 2012, 5, 2545–2558. [CrossRef] Energies 2020, 13, 304 26. 27. 28. 29. 30. 16 of 16 Florkowski, M.; FurgaΕ, J.; Kuniewski, M.; Pajak, Λ P. Propagation of lightning, oscillating and non-standard impulse waveforms in transformer windings. In The International Symposium on High Voltage Engineering; Springer: Cham, Switzerland, 2019. Xu, B.; Li, Y.; Zhao, J.; Wang, X.; Zhang, R. Simulation of propagation characteristic of ultra high frequency signals in power transformers using finite difference time domain method. In Proceedings of the 2015 5th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), Changsha, China, 26–29 November 2015; pp. 1591–1594. Wilcox, D.J.; Conlon, M.; Hurley, W.G. Calculation of self and mutual impedances for coils in ferromagnetic cores. IEE Proc. 1988, 135, 470–476. [CrossRef] Yang, Q.; Su, P.; Chen, Y. Comparison of Impulse Wave and Sweep Frequency Response Analysis Methods for Diagnosis of Transformer Winding Faults. Energies 2017, 10, 431. [CrossRef] Metal Oxide Surge Arresters Type POLIM-D, ABB Power Distribution. Available online: https://new. abb.com/high-voltage/surge-arresters/medium-voltage-arresters/distribution-systems/polim-d (accessed on 8 November 2019). © 2020 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).